INSTALLATION INSTRUCTIONS EXIT CHECK DELAYED EGRESS EMLOCK 1581S
Operation The exit door is normally closed and latched. The Model 1581S Exit Check secures the door in the locked mode with the Green LED indicating locked status. Releasing the door latch and applying up to 15lb. of pressure to the door provides a pre-activation warning beeping tone. When the nuisance delay time is exceeded, the Exit Check begins the irreversible door release cycle. At this time, the warning beeping tone changes, the LED changes to Amber, and an alarm output is provided to alert personnel of an unauthorized exit. The Exit Check will release after the 15 second delay cycle (allowing for free egress), the LED will then indicate Red and a steady warning tone will sound until the Exit Check is reset by authorized personnel.
PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS.
Single Door Installation
PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS.
PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS.
Double Door Installation (Requires two units)
O:/INST_INST2004/Installation Instructions QXD/Delayed Egress Departure Alert/INST - 1580S/INST - 1581S.vsd1
Exit Check – Model 1581S Standard Features • 650 lbs Holding Force. • 15 second exit delay. • 0-2 second nuisance delay. • Subdued alarm with 2 distinct tones -Alarm activation - intermittent -Door release - continuous • Choice of activation trigger -Door movement -Mechanical exit device with switch -Exit sense bar • Vandal resistant proximity sensor trigger. • Auto sensing 12/24VDC input. • Current: 320 mA @ 24VDC 500 mA @ 12VDC • Low power consumption. • 9 foot cable. • Size: 10"L x 2"H x 2-3/8"D Slave Lock Output The slave lock output enables the use of two units for pairs of doors and ensures that pushing on one door leaf will cause both doors to release. Inputs & Outputs • Emergency release input • Sustained bypass input • Access control / REX input, timed • Door secure / unlocked output • Alarm activation output • Door Position Status (optional) • Magnetic Bond Sensor (optional)
702RU-6 Reset Keyswitch
101-AKU Reset & sustained bypass with lock status LED
Selectable Automatic and Manual Power-Up Feature. • Auto power up occurs when power is restored and/or the fire panel is reset. • Manual Power-up is a UBC & California Building code compliant feature. Only after power restoration and fire panel reset may the lock be reset manually at the opening. A power-up key switch or keypad is required adjacent to the door. Building & Fire Life Safety Code Compliant The Exit Check 1581S complies with all national building & fire life safety codes. IBC International Building Code IFC International Fire Code NFPA 101 Life safety code NFPA 1, UFC, Uniform Fire Code UBC Uniform Building Code CBC California Building Code SBC Standard Building Code BOCA National Building Code and Chicago Building Code compliance is optional UL Listed Special Locking Arrangements
928 EntryCheck Digital Keypad Provides for 3 control functions • Alarm Reset • Manual Power-Up • Momentary or sustained bypass
O:/INST_INST2004/Installation Instructions QXD/Delayed Egress Departure Alert/INST - 1580S/INST - 1581S.vsd2
101-4AM 4 Stn remote annunciator
1. Inspect the frame to determine if an angle bracket or filler plate is required. See figure 1A, 1B, 1C.
FIG. 1B With Filler Plate
FIG. 1A Regular
FIG. 1C With Angle Bracket
FIG. 2B HOLLOW METAL DOOR From Sexnut side of door, drill exactly 31/64” hole thru one metal thickness only. From Armature side of door, drill 5/8” hole to insert reinforcement tube. Press in sexnut and reinforcement tube all the way and mount armature to door using hardware provided per Figure 2B.
2. Fold template as indicated by the dotted line. Locate template against the door and header on the lock jamb side of frame. 3. Mark frame and drill holes as indicated by template. 4. Drill holes as marked. 5. Mount armature to door. See Fig. 2A, 2B, 2C, 2D. 6. Install mounting plate to header with five #10 flat head screws provided. 7. Secure 1/4-20 socket head screws encased in lock. 8. Tighten all screws. Install anti-tamper plugs over socket head mounting screws, using a soft hammer to avoid damage to lock case. 9. Remove electronics cover. Wiring diagram inside
FIGURE 2C REINFORCED ALUMINUM OR HOLLOW METAL DOORS Use letter “F” drill and tap for 5/16-18 machine screw. Mount armature to door with hardware provided per illustration 2C.
FIG. 2A SOLID DOOR Drill exactly 31/64” thru door. From sexnut side of door drill 1/2” dia. hole 1” deep. Mount armature to door with hardware provided per illustration 2A.
O:/INST_INST2004/Installation Instructions QXD/Delayed Egress Departure Alert/INST - 1580S/INST - 1581S.vsd3
FIGURE 2D ALUMINUM DOORS Drill 21/64 hole thru door. From sexnut side of door drill 31/64 diameter hole. Mount armature to door with hardware provided per illustration 2D.
LOOSEN
TIGHTEN
O:/INST_INST2004/Installation Instructions QXD/Delayed Egress Departure Alert/INST - 1580S/INST - 1581S.vsd4
WARNINGS 1) THIS PRODUCT USES DOOR MOVEMENT TO TRIGGER THE ALARM. YOU MUST HAVE A LATCHING DEVICE SECURING THE DOOR TO PREVENT FALSE TRIGGERING. 2) USE THE SUPPLIED MOUNTING TEMPLATE TO INSTALL THIS LOCK. PROPER ALIGNMENT IS REQUIRED FOR PROPER OPERATION 3) MEASURE INPUT VOLTAGE BEFORE POWERING THE LOCK. THIS UNIT REQUIRES 12VDC OR 24VDC (+/- 10%). EXCEEDING THESE SPECIFICATIONS IS CONSIDERED OVER VOLTAGE AND WILL VOID THE WARRANTY. 4) THE LOCK CONTROL WIRES USED FOR RESET, BYPASS AND REMOTE TRIGGER, MUST ONLY BE TRIGGER BY A DRY CONTACT CLOSURE TO POWER SUPPLY (-). APPLYING VOLTAGE TO THESE WIRES WILL DAMAGE UNIT AND VOID THE WARRANTY. 5) KEEP THE MAGNETIC SURFACES OF THE CORE AND ARMATURE CLEAN AND FREE OF CORROSION FOR MAXIMUM HOLDING STRENGTH. PERIODIC MAINTENANCE SHOULD BE PERFORMED BY WIPING BOTH SURFACES WITH A CLEAN CLOTH USING LPS-3. P:\INSTALLATION INSTRUCTIONS\DELAYED EGRESS\1581S\1581S-WARNINGS.vsd
WARNINGS 1) THIS PRODUCT USES DOOR MOVEMENT TO TRIGGER THE ALARM. YOU MUST HAVE A LATCHING DEVICE SECURING THE DOOR TO PREVENT FALSE TRIGGERING. 2) USE THE SUPPLIED MOUNTING TEMPLATE TO INSTALL THIS LOCK. PROPER ALIGNMENT IS REQUIRED FOR PROPER OPERATION 3) MEASURE INPUT VOLTAGE BEFORE POWERING THE LOCK. THIS UNIT REQUIRES 12VDC OR 24VDC (+/- 10%). EXCEEDING THESE SPECIFICATIONS IS CONSIDERED OVER VOLTAGE AND WILL VOID THE WARRANTY. 4) THE LOCK CONTROL WIRES USED FOR RESET, BYPASS AND REMOTE TRIGGER, MUST ONLY BE TRIGGER BY A DRY CONTACT CLOSURE TO POWER SUPPLY (-). APPLYING VOLTAGE TO THESE WIRES WILL DAMAGE UNIT AND VOID THE WARRANTY. 5) KEEP THE MAGNETIC SURFACES OF THE CORE AND ARMATURE CLEAN AND FREE OF CORROSION FOR MAXIMUM HOLDING STRENGTH. PERIODIC MAINTENANCE SHOULD BE PERFORMED BY WIPING BOTH SURFACES WITH A CLEAN CLOTH USING LPS-3.