SECURITY DOOR CONTROLS
REGULATED POWER SUPPLY INSTALLATION INSTRUCTIONS
801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 • Fax: (805) 494-8861 www.sdcsecurity.com • E-mail:
[email protected]
MODEL 631RF/631RFA
COMPONENT LOCATIONS Battery Charger Indicator
AC Power LED
Fuse
CONTROL MODULE
POWER SUPPLY BOARD
CONTROL MODULE Primary Fuse 250V 1.5Amp
BATTERY 1 4ah
CONTROL MODULE
CONTROL MODULE
CONTROL MODULE
CONTROL MODULE
BATTERY 2 4ah
STANDARD BOX
BATTERY 2 4ah or 7ah
POWER SUPPLY BOARD
BATTERY 2 4ah or 7ah
“A” OPTION BOX
FIGURE B
Battery Input
+
-
MAIN SYSTEM ON-OFF OR FIRE PANEL CONNECTION
C
+ _ Voltage Output Terminals
System Status LED
See figures b & c for examples of Master System On/Off Control OR Power Supply control from the Fire Control Panel
FIGURE A
S H O R T 12V 24V
O P E N
VOLTAGE SELECT
C
Master ON/OFF Switch (N/C)
C
Fire Panel Contact (N/C)
Voltage Adjust Note: Power must be turned off before changing voltage jumper
+
_
Min. Switch OR Contact Ratings 100mA @ 30vdc
Figure C
POWER SUPPLY SPECIFICATIONS JUMPER SET FOR 24 VDC
JUMPER SET FOR 12 VDC
Input Voltage: 115/230 VAC @ 60hz Input Current: 0.8 amps Max.
+ -
+ -
Output Voltage: 12/24VDC (Special Applications) Output Current: 1.5 amps Ripple Voltage: 0.05 Volts Max Battery Charger Max Current: 0.25 amps Maximum recommended battery size: 7ah (Replace batteries every three years) To determine standby battery capacity, refer to Batter Discharge table (INST-BDT). Compatible UL listed Fire Devices: Smoke detector manufactured by ESL, Model 521B, 521BXT with Model 506 module.
+
_
+
12VDC
12 Volt mode Battery Connections
Suitable Uses: Electric Lock Power Supply Access Control Power Supply Burglar Alarm System Power Supply
+- + -
_ Battery
TEST UNIT YEARLY P:\INSTALLATION INST\Power Supplies\INST-631RF_631RFA.vsd
Rev C
01-12
_ 12VDC
High voltage Input
631RF
+
12VDC
+
24 Volt mode Battery Connections
Wire Routing
NOT INTENDED TO POWER A LOCAL BURGLAR ALARM INDICATING DEVICE.
_
C
NOTE: Power limited cable must maintain a 1/4” or more spacing from battery cables or primary power wires. Power limited Class 2 output
REGULATED POWER SUPPLY INSTALLATION INSTRUCTIONS
801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 • Fax: (805) 494-8861 www.sdcsecurity.com • E-mail:
[email protected]
MODEL 631RF-CUL/631RFA-CUL Battery Charger Indicator
COMPONENT LOCATIONS AC Power LED
Fuse
MODEL 631RF-CUL/631RFA-CUL
CONTROL MODULE
POWER SUPPLY BOARD
CONTROL MODULE
Primary Fuse 250V 1.5 Amp
BATTERY 1 4ah
CONTROL MODULE
CONTROL MODULE
CONTROL MODULE
CONTROL MODULE
BATTERY 2 4ah or 7ah
BATTERY 1 4ah
COVER
+
Voltage Output Terminals
_
BATTERY MONITOR LEDS GRN = AC RED = BATTERIES ORG = NO/LO BATTERY
C
System Status LED YEL = System OK RED = No AC Input GRN = No DC Output
S H O R T 12V 24V Voltage Select
O P E N
Voltage Adjust
BATTERY 2 4ah or 7ah
“A” Option Box
STANDARD BOX
Battery Input
Min. Switch or Contact Ratings 100mA @ 30VDC
MAIN SYSTEM ON-OFF
Note: Power must be turned off before changing voltage jumper.
POWER SUPPLY BOARD
_
+
C
Master ON/OFF Switch (N/C)
POWER SUPPLY SPECIFICATIONS Input Voltage: 115/230 VAC @ 60hz Input Current: 0.8 amps Max.
+
+
Install Jumper
Output Voltage: 12/24VDC (Regulated) Output Current: 1.5 amps Ripple Voltage: 0.05 Volts Max. Battery Charger Max. Current: 0.25 amps Maximum recommended battery size: 7ah Recommended Battery: SDC Model RB12V7 (Replace batteries every 3 years)
Monitor Board _ _ +
+
Remove Jumper
_
+
12VDC
12VDC
+
_
12VDC
HIGH VOLTAGE INPUT
+_ +_
+
+
TEST UNIT ANNUALLY
_
24 Volt Mode Battery Connections
12 Volt Mode Battery Connections
To determine standby battery capacity refer to Battery Discharge Table (INST-BDT). Suitable Uses: Electric Lock Power Supply Access Control Power Supply
Monitor _ _ Board +
_
+
C
POWER LIMITED CLASS 2 OUTPUT
_
Battery
P:\INSTALLATION INST\Power Supplies\INST-631RF-CUL_631RFA-CUL.vsd
_
Note: Power limited cable must maintain a 1/4” or more of spacing from battery cables or primary power wires.
Rev A
04-13