POWER SUPPLY INSTALLATION INSTRUCTIONS
801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 • Fax: (805) 494-8861 www.sdcsecurity.com • E-mail:
[email protected]
MODEL 632RF
COMPONENT LOCATIONS
MODEL 632RF
CONTROL MODULE
MANUAL RESET
AC MAINS
CONTROL MODULE
SYSTEM STATUS YELLOW – SYSTEM OK RED – ON BATTERY PWR GREEN – NO DC OUTPUT
BATTERY 1 4ah
POWER SUPPLY BOARD
BATTERY 1 4ah
STANDARD BOX
-
+ _
C 24V
+
BATTERY INPUT TERMINALS
+
VOLTAGE OUTPUT TERMINALS
MAIN SYSTEM ON-OFF OR FIRE PANEL CONNECTION Min. Switch or Contact Ratings 100mA @ 30VDC
+ _
-
C
C
12V CHG
FLOAT
VOLTAGE SELECT SWITCHES
BATTERY CHARGER STATUS
Fire Panel Contact (N/C)
Master ON/OFF Switch (N/C)
POWER SUPPLY SPECIFICATIONS Input Voltage: 115/230 VAC @ 60hz Input Current: 0.8 amps Max. Output Voltage: 12/24VDC Output Voltage Ranges: 12 V Operation: 9.2 – 12.0 VDC 24 V Operation: 21.2 – 24.0 VDC Output Current: 2.0 amps Ripple Voltage: 0.05 Volts Max. Battery Charger Max. Current: 0.25 amps Maximum recommended battery size: 4ah (Replace batteries every 3 years)
+ _
+ _
12VDC
HIGH VOLTAGE INPUT
Power Supply +
_
Battery
Rev C
07-15
FOR 24VDC
12VDC
24 Volt Mode Battery Connections
12 Volt Mode Battery Connections
TEST UNIT ANNUALLY
SET
C SWITCH
12VDC
Suitable Uses: Electric Lock Power Supply Access Control Power Supply
P:\INSTALLATION INST\Power Supplies\INST-632RF.vsd
+ _
SET C SWITCH FOR + _ 12VDC
+
_
C
Note: Power limited cable must maintain a 1/4” or more of spacing from battery cables or primary power wires.
7ah batteries require an Auxiliary battery box POWER LIMITED CLASS 2 OUTPUT
801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 • Fax: (805) 494-8861 www.sdcsecurity.com • E-mail:
[email protected]
POWER SUPPLY INSTALLATION INSTRUCTIONS MODEL 632RFA
AC PRESENT
MODEL 632RFA
MANUAL RESET
COMPONENT LOCATIONS CONTROL MODULE
AC VOLTAGE INPUT
CONTROL MODULE
SYSTEM STATUS YELLOW – SYSTEM OK RED – ON BATTERY PWR GREEN – NO DC OUTPUT
BATTERY 1 4ah
POWER SUPPLY BOARD
BATTERY 1 4ah
STANDARD BOX
-
+ _
C 24V
+
BATTERY INPUT TERMINALS
+
VOLTAGE OUTPUT TERMINALS
MAIN SYSTEM ON-OFF OR FIRE PANEL CONNECTION Min. Switch or Contact Ratings 100mA @ 30VDC
+ _
-
C
C
12V CHG
FLOAT
VOLTAGE SELECT SWITCHES
BATTERY CHARGER STATUS
Fire Panel Contact (N/C)
Master ON/OFF Switch (N/C)
POWER SUPPLY SPECIFICATIONS Input Voltage: 115 VAC @ 60hz Input Current: 1.0 amps Max.
+ _
Output Voltage: 12/24VDC Output Voltage Ranges: 12 V Operation: 9.2 – 12.0 VDC 24 v Operation: 21.2 – 24.0 VDC Output Current: 2.0 amps Ripple Voltage: 0.05 Volts Max.
SET
C SWITCH + _
12VDC
12VDC
FOR 24VDC
12VDC
24 Volt Mode Battery Connections
12 Volt Mode Battery Connections
Battery Charger Max. Current: 0.25 amps Maximum recommended battery size: 4ah (Replace batteries every 3 years)
Suitable Uses: Electric Lock Power Supply Access Control Power Supply
+ _
SET C SWITCH FOR + _ 12VDC
HIGH VOLTAGE INPUT POWER LIMITED CLASS 2 OUTPUT
+ _ C + _
Battery
TEST UNIT ANNUALLY P:\INSTALLATION INST\Power Supplies\INST-632RFA.vsd
Rev A
04-13
Power Supply
Note: Power limited cable must maintain a 1/4” or more of spacing from battery cables or primary power wires.
7ah batteries require an Auxiliary battery box