POWER SUPPLY INSTALLATION INSTRUCTIONS

801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 • Fax: (805) 494-8861 www.sdcsecurity.com • E-mail: [email protected]

MODEL 632RF

COMPONENT LOCATIONS

MODEL 632RF

CONTROL MODULE

MANUAL RESET

AC MAINS

CONTROL MODULE

SYSTEM STATUS YELLOW – SYSTEM OK RED – ON BATTERY PWR GREEN – NO DC OUTPUT

BATTERY 1 4ah

POWER SUPPLY BOARD

BATTERY 1 4ah

STANDARD BOX

-

+ _

C 24V

+

BATTERY INPUT TERMINALS

+

VOLTAGE OUTPUT TERMINALS

MAIN SYSTEM ON-OFF OR FIRE PANEL CONNECTION Min. Switch or Contact Ratings 100mA @ 30VDC

+ _

-

C

C

12V CHG

FLOAT

VOLTAGE SELECT SWITCHES

BATTERY CHARGER STATUS

Fire Panel Contact (N/C)

Master ON/OFF Switch (N/C)

POWER SUPPLY SPECIFICATIONS Input Voltage: 115/230 VAC @ 60hz Input Current: 0.8 amps Max. Output Voltage: 12/24VDC Output Voltage Ranges: 12 V Operation: 9.2 – 12.0 VDC 24 V Operation: 21.2 – 24.0 VDC Output Current: 2.0 amps Ripple Voltage: 0.05 Volts Max. Battery Charger Max. Current: 0.25 amps Maximum recommended battery size: 4ah (Replace batteries every 3 years)

+ _

+ _

12VDC

HIGH VOLTAGE INPUT

Power Supply +

_

Battery

Rev C

07-15

FOR 24VDC

12VDC

24 Volt Mode Battery Connections

12 Volt Mode Battery Connections

TEST UNIT ANNUALLY

SET

C SWITCH

12VDC

Suitable Uses: Electric Lock Power Supply Access Control Power Supply

P:\INSTALLATION INST\Power Supplies\INST-632RF.vsd

+ _

SET C SWITCH FOR + _ 12VDC

+

_

C

Note: Power limited cable must maintain a 1/4” or more of spacing from battery cables or primary power wires.

7ah batteries require an Auxiliary battery box POWER LIMITED CLASS 2 OUTPUT

801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 • Fax: (805) 494-8861 www.sdcsecurity.com • E-mail: [email protected]

POWER SUPPLY INSTALLATION INSTRUCTIONS MODEL 632RFA

AC PRESENT

MODEL 632RFA

MANUAL RESET

COMPONENT LOCATIONS CONTROL MODULE

AC VOLTAGE INPUT

CONTROL MODULE

SYSTEM STATUS YELLOW – SYSTEM OK RED – ON BATTERY PWR GREEN – NO DC OUTPUT

BATTERY 1 4ah

POWER SUPPLY BOARD

BATTERY 1 4ah

STANDARD BOX

-

+ _

C 24V

+

BATTERY INPUT TERMINALS

+

VOLTAGE OUTPUT TERMINALS

MAIN SYSTEM ON-OFF OR FIRE PANEL CONNECTION Min. Switch or Contact Ratings 100mA @ 30VDC

+ _

-

C

C

12V CHG

FLOAT

VOLTAGE SELECT SWITCHES

BATTERY CHARGER STATUS

Fire Panel Contact (N/C)

Master ON/OFF Switch (N/C)

POWER SUPPLY SPECIFICATIONS Input Voltage: 115 VAC @ 60hz Input Current: 1.0 amps Max.

+ _

Output Voltage: 12/24VDC Output Voltage Ranges: 12 V Operation: 9.2 – 12.0 VDC 24 v Operation: 21.2 – 24.0 VDC Output Current: 2.0 amps Ripple Voltage: 0.05 Volts Max.

SET

C SWITCH + _

12VDC

12VDC

FOR 24VDC

12VDC

24 Volt Mode Battery Connections

12 Volt Mode Battery Connections

Battery Charger Max. Current: 0.25 amps Maximum recommended battery size: 4ah (Replace batteries every 3 years)

Suitable Uses: Electric Lock Power Supply Access Control Power Supply

+ _

SET C SWITCH FOR + _ 12VDC

HIGH VOLTAGE INPUT POWER LIMITED CLASS 2 OUTPUT

+ _ C + _

Battery

TEST UNIT ANNUALLY P:\INSTALLATION INST\Power Supplies\INST-632RFA.vsd

Rev A

04-13

Power Supply

Note: Power limited cable must maintain a 1/4” or more of spacing from battery cables or primary power wires.

7ah batteries require an Auxiliary battery box